EasyManua.ls Logo

Siemens LME71.000A1 - Page 200

Siemens LME71.000A1
245 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
200/245
Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 24 Error code list with operation via external AZL2... display 29.11.2011
PWM (P675.00) after reaching the prepurge speed,
or
- After reaching the ignition load speed, the
maximum ignition load PWM (P675.01) was
exceeded
Loc: 226 PWM fan faulty
Parameterization error:
- Speed low-fire > speed high-fire, or
- Low-fire = 0 rpm, or
- Maximum speed = 0 rpm
Loc: 227 PWM fan faulty
One or several parameters violate the
minimum/maximum limit
rSt Er1
Error in compatibility program module to basic
unit during restore process
- Program sequence of program module does not
match the basic unit
rSt Er2
Error in compatibility program module to basic
unit during restore process
- Hardware of basic unit does not match the
program module
rSt Er3 Error during restore process
- Program module faulty
- Program module removed during restore
process

Table of Contents

Related product manuals