EasyManua.ls Logo

Siemens LMV50 series

Siemens LMV50 series
327 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
124/327
Building Technologies Basic Documentation LMV5... CC1P7550en
7 Boiler controller / load controller 22.05.2018
If the internal temperature limiter function is used, the time constant «T» of the
temperature sensor with protection pocket must not exceed 45 seconds.
7550d19E/0502
1
T
Ι
0.63
Temperature
Ι
M
X
a
Time t
Figure 60: Instant temperature change of test medium to determine the time constant
Legend
Ι
M
Temperature of test medium
X
a
Output signal of temperature sensor
T Time constant
Requirements placed on
sensor and protection
pocket

Table of Contents

Other manuals for Siemens LMV50 series

Related product manuals