Building Technologies Basic Documentation LMV5... CC1P7550en
15 Technical data 22.05.2018
15.5 CAN bus cable
Types of cable
AGG5.641 8 mm dia. +0,5 / -0,2 mm
Bending radius: 120 mm
Ambient temperature: -30...+70 °C
(cable not moving)
Cable jacket resistant to almost all types
of mineral oil
AGG5.631 7.5 mm dia. ±0.2 mm
Bending radius: 113 mm
Ambient temperature: -30...+70 °C
(cable not moving)
Cable jacket resistant to almost all types
of mineral oil
15.6 Environmental conditions (for all LMV5
components)
Storage DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...60 °C
Humidity <95% r.h.
Transport DIN EN 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -20...60 °C
Humidity <95% r.h.
Operation DIN EN 60721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
Temperature range -20...60 °C
Humidity <95% r.h.
Caution!
Condensation, formation of ice and ingress of water are not permitted!