Building Technologies Basic Documentation LMV5... CC1P7550en
20 Flue gas recirculation (FGR) function (LMV50/LMV51.3/LMV52) 22.05.2018
If auxiliary actuator 3 still maintains the ignition position (recirculation duct CLOSED), it
is marked with #.
The position value of auxiliary actuator 3 can be changed, but the actuator will not
follow the readjustment for that period of time!
The changed value can also be stored.
If auxiliary actuator 3 is not marked with # when making the setting, it is already on the
ratio control curve, in which case it also follows the readjustment of the position value. If
marked with # or in case of selection without driving, the curve position can be
readjusted without having the actuator following the position value.
Β
Note!
During the time the curve menu is used, the state of the flue gas recirculation (FGR)
function does not change. This means that if auxiliary actuator 3 is still at the Flue Gas
Recirc. position (ignition position) when activating the parameterization of curves, and
it maintains that position until parameterization is completed.