Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
127/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
StartReleaseOil Input start release oil active deactivated
activated
OEM activated x x
AirPressureTest Assess / ignore air pressure signal deactivated
activated
OEM activated x x
PS-VP/CPI Configuration of input on PM-VP or CPI PS-VP
CPI Gas
CPI Gas + Oil
CPI Oil
OEM PS-VP x x
FGR-PS/FCC Configuration of input for FCC or FGR-PS FCC
FGR-PS
deactivated
OEM FCC x x
InputController Input controller active deactivated
activated
OEM activated x x
GasPressureMin Input minimum gas pressure (+start release gas) active deactivated
activated
deact xOGP
OEM activated x x
GasPressure-
Max
Input maximum gas pressure active deactivated
activated
OEM activated x x
OilPressureMin Input minimum oil pressure active deactivated
activated
act from ts
OEM activated x x
OilPressureMax Input oil pressure max. active deactivated
activated
OEM activated x x
HeavyOilDirStart Input immediate heavy oil start active deactivated
activated
OEM activated x x
Start/PS-Valve Configuration of output for start signal or PS relief valve StartSignal
PS Relief
PS Reli_Inv
OEM StartSignal x x
ConfigFlameDet Configuring the flame detector User x x
ReacExtranLight Reaction in the event of extraneous light in standby Lockout
Startblock
OEM Startbllock x x
FlameSignal Configuring the flame signal User x x
Standardize Standardizing the flame signal OEM x x
StandardFactor Reading / reseting the standard factor OEM x x
FlameSig QRI_B Flame signal QRI_B 0...255 User --- x
FlameSig ION Flame signal ION 0...255 User --- x