Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
128/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
SensExtranlGas QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
1 Sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
OEM 1 sensor x
SensPilotPhGas QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
QRI (QRB) AND ionization
1 Sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
QRI_B & ION
OEM 1 sensor x
SensOperPhGas QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
QRI (QRB) AND ionization
1 Sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
QRI_B & ION
OEM 1 sensor x
SensExtranlOil QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
1 Sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
OEM 1 sensor x
SensPilotPhOil QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOT QRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
1 Sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
OEM 1 sensor x