Only rotate the panel in a way that does not cause pinching of the cables.
Route all of the cables in such a way that they do not come into contact with chafing edges.
Note
Warning for areas subject to NEC or CEC:
Safety notice for connectors with Ethernet marking:
A Ethernet or Ethernet segment, with all its associated interconnected equipment, shall be
entirely contained within a single low-voltage power distribution and within a single building.
The Ethernet is considered to be in an "environment A" according IEEE802.3 or "environment
0" according IEC TR 62102, respectively.
Never make direct electrical connection to TNV-circuits (Telephone Network) or WAN (Wide
Area Network).
Pin assignment
The pin assignments of the interfaces are described in Section "Connect" > "Pin assignment
of the interfaces" (Page 37).
Power supply connector for MCP 398C
Connection type Strain-relief clamp connection
Connection screw M2.5 screw with cross-slot
Operating tool Screwdriver blade 0.6x3.5, PH0, PZ0 (DIN
5264, ISO 8764/2-PH, ISO 8764/2-PZ)
Specified tightening torque Nm 0.4 ... 0.5
Conductor cross-section min./max.
Solid mm² 1.3 … 3.3
Finely stranded mm² 1.3 … 3.3
With ferrule with collar DIN46228/4 mm² 1.3 … 2.5
With ferrule DIN46228/1 mm² 1.3 … 3.3
AWG cables, solid or stranded AWG 12 … 16
Description
2.3 Interfaces
Machine control panel: MCP 398C
14 Manual, 12/2017, A5E43199783B AA