1 2 3 4 5 6 7 8 9 10 Meaning
on on on off on on on off Default device name: mcp-pn119
off on on off on on on off Default device name: mcp-pn118
on off on off on on on off Default device name: mcp-pn117
off off on off on on on off Default device name: mcp-pn116
on on off off on on on off Default device name: mcp-pn115
off on off off on on on off Default device name: mcp-pn114
on off off off on on on off Default device name: mcp-pn113
off off off off on on on off Default device name: mcp-pn112
x x x x x x x x "
on on on on off off off off Default device name: mcp-pn15
off on on on off off off off Default device name: mcp-pn14
on off on on off off off off Default device name: mcp-pn13
off off on on off off off off Default device name: mcp-pn12
on on off on off off off off Default device name: mcp-pn11
off on off on off off off off Default device name: mcp-pn10
on off off on off off off off Default device name: mcp-pn9
off off off on off off off off Default device name: mcp-pn8
on on on off off off off off Default device name: mcp-pn7
off on on off off off off off Default device name: mcp-pn6
on off on off off off off off Default device name: mcp-pn5
off off on off off off off off Default device name: mcp-pn4
on on off off off off off off Default device name: mcp-pn3
off on off off off off off off Default device name: mcp-pn2
on off off off off off off off Default device name: mcp-pn1
off off off off off off off off Default device name: mcp-pn
MCP set up as IE
You can assign a logical address to the MCP for communication via Ethernet with the 10-bit
switch S1.
Table 2-5 Setting of switch S1 as delivered
1 2 3 4 5 6 7 8 9 10 Meaning
off off off off off off on on off off MCP address 192
The two switches S1-9 and S1-10 must be set to "off" (IE functionality).
The switches S1-1 to S1-8 define the MCP address in the range of 0 to 255.
The addresses from 192 to 223 count as the default range.