G85139-H1751-U529-D1G85139-H1751-U529-D1
© Siemens plc 1999© Siemens plc 1999
Make sure that the input power supply is isolated before making or changing any connections toMake sure that the input power supply is isolated before making or changing any connections to
Ensure that the motor is configured for the correct supply voltage. Single/three phase 230 V unitsEnsure that the motor is configured for the correct supply voltage. Single/three phase 230 V units
must not be connected to a 400 V three phase supply.must not be connected to a 400 V three phase supply.
When  synchronous  machines  are  connected  or  when  coupling  several  motors  in  parallel,  theWhen  synchronous  machines  are  connected  or  when  coupling  several  motors  in  parallel,  the
inverter  must  be  operated  with  voltage/frequency  control  characteristic  (P077=  0  or  2)  and  slipinverter  must  be  operated  with  voltage/frequency  control  characteristic  (P077=  0  or  2)  and  slip
compensation must be disabled (P071 = 0).compensation must be disabled (P071 = 0).
This equipment is suitable for use in a circuit capable of delivering not more than 100,000This equipment is suitable for use in a circuit capable of delivering not more than 100,000
symmetrical amperes (rms), for a maximum voltage of 230 / 460 V * when protected by asymmetrical amperes (rms), for a maximum voltage of 230 / 460 V * when protected by a
time delay fuse *.time delay fuse *.
* As detailed in section 8.* As detailed in section 8.
: the power terminals are directly available beneath the inverter. For the control terminals lift: the power terminals are directly available beneath the inverter. For the control terminals lift
the front cover the front cover 
of the inverter. of the inverter. 
Frame size B:Frame size B:
use a small bladed screwdriver (use a small bladed screwdriver (
as shown in Figure 2.2.2as shown in Figure 2.2.2
) to release the terminal cover of) to release the terminal cover of
the inverter and allow it to the inverter and allow it to 
swing down to hang beneath the swing down to hang beneath the 
Frame size C:Frame size C:
use a small bladed screwdriver (use a small bladed screwdriver (
as shown in Figure 2.2.3as shown in Figure 2.2.3
) to release the gland plate and the) to release the gland plate and the
fan housing; allow them both to swing down to hang beneath the inverter.fan housing; allow them both to swing down to hang beneath the inverter.
Connect  the  cables  to  the  power  and  control  terminals  in  accordance  with  the  information  supplied  in  thisConnect  the  cables  to  the  power  and  control  terminals  in  accordance  with  the  information  supplied  in  this
Ensure that the leads are connected correctly and the Ensure that the leads are connected correctly and the 
equipment is properly earthed.equipment is properly earthed.
The control, power supply and motor leads must be laid separately. They must not be fed throughThe control, power supply and motor leads must be laid separately. They must not be fed through
the same cable conduit/trunking.the same cable conduit/trunking.
High voltage insulation test equipment must not be used on cables connected to the inverter.High voltage insulation test equipment must not be used on cables connected to the inverter.
Use screened  cable  for  the  control  cable,  Class  1  60/75Use screened  cable  for  the  control  cable,  Class  1  60/75
C  copper  wire  only. Tightening torque  for  the  fieldC  copper  wire  only. Tightening torque  for  the  field
wiring terminals is 1.1 Nm.wiring terminals is 1.1 Nm.
A small bladed screwdriver, max. 3.5 mm will be required to operate the control terminal WAGO cable clampA small bladed screwdriver, max. 3.5 mm will be required to operate the control terminal WAGO cable clamp
connectors as shown inconnectors as shown in
To tighten up the power and motor terminalTo tighten up the power and motor terminal
screws use a screws use a 
mm cross-tip screwdriver.mm cross-tip screwdriver.
When all power and control connections are complete:When all power and control connections are complete:
lower the flap in lower the flap in 
the front cover of the front cover of 
the inverter.the inverter.
Frame size B :Frame size B :
lift and secure the lift and secure the 
terminal cover to the iterminal cover to the i
Frame size C :Frame size C :
lift and secure the lift and secure the 
gland plate and the gland plate and the 
fan housing to the fan housing to the