Accessing the connection compartment through the front
156 NXAIR M 139-2021.9 / 07
Fig. 263: Panel versions with panel width 800 mm : 15 bolted joints
Panel versions with withdrawable circuit-breaker, withdrawable circuit-breaker / fuse combination
or withdrawable disconnector link only:
Install the protection plate of the switching-device compartment (1).
To fix the protection plate of the switching-device compartment (1), tighten the nuts (5) hand-
tight.
4 nuts M8 with contact washers
Tighten the fixing bolts (5) with a tightening torque of 25 Nm.
Fig. 264: 4 bolted joints on protection plate of switching-device compartment
The partition between the connection compartment and the switching-device compartment
is installed.