Panels with motor operating mechanism control
139-2021.9 / 07 NXAIR M 235
23.19 Technical data / operating times
Voltage supply for
control circuit and motor circuit
Wide-voltage range 24 V DC / 48 V DC / 60 V DC /
110 V DC / 220 V DC / 110 V AC / 230 V AC
Control and motor circuit are executed separately
Voltage fluctuations in the range from 0.85 × U
n
to
1.1 × U
n
are permissible
Power consumption of control circuit
< 100 mA in operating mode
Energizing when the command is given
Until the motor starts up > 180 ms
Power consumption of geared motor for
racking function
110 V DC:
Motor starting current, approx. 6.5 A
Continuous motor current while racking, approx. 1 A
Motor power, approx. 1.2 W
Further values on request.
Motor running time for racking function
Feedback monitoring time for racking
valid switching functions:
racking to service or test position
After giving the command and when a motor has
started, a fault signal is issued if the feedback
contacts detect no end position within 65 s.
Fault indication and fault evaluation according to
chapter 23.20.