Operating the circuit-breaker panel
40 NXAIR M 139-2021.9 / 07
10.9 Closing the circuit-breaker electrically
NOTICE
Conflicting operation
Operating the circuit-breaker electrically is possible locally or from a central
control. The requirement of setting the panel to either local or remote control
prevents operating the panel locally and centrally at the same time.
Depending on the intended operating mode, set the panel to either local or
remote control (for example by switching the local-remote switch).
HINT
If an undervoltage release is fitted, it must be connected to the auxiliary voltage for
the switching operation, as otherwise closing is not possible.
HINT
Unexpected motor noise and vibration
Operating the circuit-breaker discharges and/or charges the spring energy store
abruptly. This causes a short loud noise and low vibration.
Expect switching noise and low vibration from inside the circuit-breaker.
HINT
The opening spring is charged during the closing operation.
Preconditions
Withdrawable circuit-breaker in service position or in test position
Circuit-breaker in OPEN position
Spring state indicator for the closing spring shows CHARGED
High-voltage door closed
Auxiliary voltage for the panel connected
Remote or local control
Procedure
Close the circuit-breaker via central or local electrical control element.