Fitting the earthing device
139-2021.9 / 07 NXAIR M 201
22.3 Removing the earthing device
DANGER
Electric shock
Put on personal protective equipment.
Preconditions
Bushing contacts isolated
Earthing rod available
Slip-on lever for opening the shutter available
Personal protective equipment put on
Fig. 340: Earthing device to be removed
Detaching the earthing device from the bushing contacts
Hereafter, it is exemplarily shown how to detach the earthing device from the bushing contacts in the upper
row of bushings linked with the busbar compartment. Proceed in the same way when detaching the
earthing device from the bushing contacts in the lower row of bushings linked with the connection
compartment.
DANGER
Electric shock
Always observe the Five Safety Rules.
Exclusively use the associated earthing rod for detaching the earthing
tulips from the bushing contacts.
Use the earthing accessories only in the way described hereafter. Never
reach out beyond the limiting ring on the earthing rod. This ensures a safe
distance to the bushing contacts.