Operating the removable voltage transformers
139-2021.9 / 07 NXAIR M 105
15.3 Racking the removable voltage transformers to service position
NOTICE
Maloperation
If the removable voltage transformers are not correctly positioned in the panel,
damages may occur when the removable voltage transformers are racked.
If you hear a noise or if you notice a resistance, stop racking immediately.
Inform the regional Siemens representative.
Fig. 165: Racking tool for the removable voltage transformers
Preconditions
Removable voltage transformers inserted in the panel
Low-voltage connector plugged on
High-voltage door closed
Racking tool available
Key for padlock available
The actuating opening for racking the removable voltage transformers is located on the control board of the
high-voltage door.
Fig. 166: Actuating opening for racking the removable voltage transformers