Fitting the earthing device
139-2021.9 / 07 NXAIR M 195
Impermissibly high voltage and current
Inappropriate use of the earthing accessories will result in impermissibly high
voltage and current.
Use the earthing device exclusively for the maximum permissible short-
circuit current and the maximum permissible short-circuit duration.
Do not use the earthing device for short-circuit tests or purposes causing
similarly high voltages and currents.
Perform diligent inspection of the earthing accessories before each
application.
Preconditions
Withdrawable part taken out of the panel
Low-voltage connector stowed away
Both shutter to the connection compartment and shutter to the busbar compartment closed
Bushing contacts to be earthed isolated
Earthing accessories available and in perfect condition
Slip-on lever for opening the shutter available
Padlock for shutter not to be used available
Personal protective equipment put on
Upper shutter covering bushing
contacts linked with busbar
compartment
Lower shutter covering bushing
contacts linked with connection
compartment
Fig. 330: Fixed earthing point for connecting the
earthing clamp