EasyManua.ls Logo

Siemens NXAIR M - Page 208

Siemens NXAIR M
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panels with motor operating mechanism control
208 NXAIR M 139-2021.9 / 07
Several electrical interlocks support safe electrical operation:
Operating option
Preconditions for operating option
Electrical interlocking
Racking the withdrawable
circuit-breaker to test position
electrically
Low-voltage connector plugged
on
High-voltage door closed
Feeder earthing switch in OPEN
position
Circuit-breaker in OPEN position
Access is released for
motor-operated racking
Control door closed
During an ongoing racking
procedure, racking in opposite
direction is interlocked
electrically.
During an ongoing racking
procedure, opening / closing the
circuit-breaker is interlocked
electrically.
During an ongoing racking
procedure, opening / closing the
feeder earthing switch
is interlocked electrically.
Opening / closing the circuit-
breaker electrically for testing
purposes
Low-voltage connector plugged
on
High-voltage door closed
Control door closed
Withdrawable circuit-breaker
in test position
Opening / closing the circuit-
breaker electrically for testing
purposes is not interlocked
electrically.
Opening / closing the circuit-
breaker electrically during
service
Low-voltage connector plugged
on
High-voltage door closed
Control door closed
Withdrawable circuit-breaker
in service position
Opening / closing the circuit-
breaker electrically during
service for testing purposes is
not interlocked electrically.
Opening / closing the feeder
earthing switch electrically for
testing purposes
Low-voltage connector plugged
on
High-voltage door closed
Control door closed
Withdrawable circuit-breaker
in test position
Opening / closing the feeder
earthing switch electrically for
testing purposes is
not interlocked electrically.
Closing the feeder
earthing switch electrically
during service
Low-voltage connector plugged
on
High-voltage door closed
Control door closed
Withdrawable circuit-breaker
in service position
Closing the feeder earthing switch
electrically during service is
interlocked electrically.

Table of Contents

Related product manuals