EasyManua.ls Logo

Siemens OH110 - Technical Data for Smoke Detector OP110

Siemens OH110
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
Specifications
Technical data for smoke detector OP110
52
Building Technologies A6V10316298_e_en_--
Fire Safety 2014-05-21
Ambient conditions
Operating temperature/permissible
ambient temperature
-10…+50 °C
Storage temperature -30…+70 °C
Air humidity 95 % rel.
Protection categories according to
EN 60529 / IEC 60529:
l Bases DB110, DB110x, DB110xx
(all installation types)
IP40
l Bases DB110, DB110x, DB110xx
with detector base seal RS720
IP42
l Bases DB110, DB110x, DB110xx
with base attachment wet BA721
IP44
Electromagnetic compatibility:
l 10 kHz…1.8 GHz 50 V/m
l 1.8 GHz…2.5 GHz 20 V/m
Mechanical data Color RAL 9010 pure white
Standards European standards l CEA 4021
l EN 54-7
8.2 Technical data for smoke detector OP110
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
l Document A6V10301051
Detector line Operating voltage DC 16…28 V
Maximum current connection factor 1
Quiescent current at maximum current
connection factor
Max. 100 μA
Surge current at maximum current
connection factor
160 μA
Alarm voltage at:
l Alarm current = 1…15 mA DC 5…10 V
l Alarm current = 35 mA DC 18…22 V
l Alarm current = 50 mA DC 26…28 V
Alarm current at operating voltage
UB = DC 5…28 V
4…50 mA
Reset voltage UR:
l Alarm is reliably reset DC 0…2 V
l Alarm may possibly not be reset DC 2…4 V
Protocol Collective (with and without current limitation)
Compatibility See 'List of compatibility'
External alarm indicators
Number of external alarm indicators that
can be connected
Max. 2
Voltage DC 9…30 V
Current 10…16 mA