4.5 Power-Up ProtoAir
Check power requirements in the table below:
Power Requirement for ProtoAir External Gateway
Current Draw Type
ProtoAir Family
12VDC
24V DC/AC
FPA-W44 (Typical)
250mA
125mA
NOTE: These values are ‘nominal’ and a safety margin should be added to the power supply of
the host system. A safety margin of 25% is recommended.
Figure 10: Required Current Draw for the ProtoAir
Apply power to the ProtoAir as shown below in Figure 11. Ensure that the power supply used complies
with the specifications provided in Appendix D.1.
The ProtoAir accepts 12-24VDC or 24VAC on pins 4 and 5.
Frame GND should be connected.
Power to
ProtoAir
ProtoAir
Pin #
Pin
Assignment
Power In (+)
Pin 4
V +
Power In (-)
Pin 5
V -
Frame Ground
Pin 6
FRAME GND
Figure 11: Power Connections