The "Clean filter reminder" function counts the fan operating hours and displays
message " FIL" to remind the user to clean the fan filter as soon as the threshold
is reached. This does not impact the thermostat's operation, which continues to run
normally. The function is set using P62 (default = OFF (0)).
The "Clean filter reminder" function can be removed using +/ – when viewing
alarms on the INFO page.
In Auto Timer mode , the default fan mode is automatic. It can be changed to
Manual by touching the icon. The fan returns to the automatic default mode
after each switchover from Comfort to Economy mode, and vice versa.
To let the heating/cooling coil reach its temperature, the fan start can be delayed by
a time period set via P67.