EasyManua.ls Logo

Siemens RDF800KN Series

Siemens RDF800KN Series
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58 / 94
Siemens RDF800KN.., RDF800KN/VB, RDD810KN/NF Basic documentation CE1P3174en
Smart Infrastructure 2020-02-21
The table below shows the error code and default alarm texts.
Thermostat
Fault information on
the
bus
Prio
rity
Fault
/
s
ervice
Display
Error code
Default fault text
Text adjustable
*)
-
No fault
---
0
No fault
ü
1 Bus power supply
**)
BUS
5000 No bus power supply ---
2 Device address error
ADR
6001 > 1 id device address ---
3 Condensation
CON
4930 Condensation ü
4 External fault input X1
AL1
9001 Fault input 1 ü
5 External fault input X2
AL2
9002 Fault input 2 ü
6 Clean filter reminder
FIL
3911 Dirty filter ü
*)
Default alarm texts are stored in the thermostat’s non-volatile memory and can be adjusted using
the ACS tool.
**)
This error will not be sent via the bus (because there is either no bus, not sufficient bus power
supply, the bus is overloaded or the bus signal is distorted).
· Priority order is 1…6.
· External faults 4…5. If faults are active, AL1 and AL2 display alternately. Only
the fault with the highest priority will be sent via the bus.
A supervisory alarm system may command the thermostat to stop sending fault
signals to the bus using the communication object "Fault transmission"
(disable/enable).
This has no impact on the local display of faults.
After a timeout of 48 hours, the forwarding of fault signals will automatically be
enabled again.
Priority of alarms
Fault transmission

Table of Contents

Related product manuals