[dw_7SR5_function67SettingExample2, 1, en_US]
Figure 5-34
Application of Directional Overcurrent Protection
[dw_7SR5_function67SettingExample3, 1, en_US]
Figure 5-35
Feeder Fault on Interconnected Network
Considering the D-G feeder fault shown in Figure 5-35: the current magnitude through breakers C and D will
be similar and their associated relays will have similar prospective operate times. To ensure that only the