EasyManua.ls Logo

Siemens Reyrolle 7SR5 - Page 301

Siemens Reyrolle 7SR5
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Settings Example
[dw_7SR5_function87GHApplicationAndSettingNotes3, 1, en_US]
Figure 5-46 Example System – Restricted Earth Fault
Plant Data
See Figure 5-46
Settings Requirements
[fo_function87TExample7, 1, en_US]
Assigned through fault current (rated stability limit) = 16 ⋅ load current = 8.4 kA, or, as specified by the user
Required Fault Setting (Primary Operate Current)
10 to 25 % of protected winding rated current, or as specified by the user
Required P.O.C. = 53 - 131 A. Say 60 A.
Line CT (LCT) and Connection Details
Turns ratio (T)
1 to 600
Voltage knee point (V
K
) 350 V
Magnetising current (Imag) @ V
K
40 mA
CT secondary resistance (R
CT
) 7.5 Ω
CT lead loop resistance (R
L
) 0.15 Ω max.
Neutral CT (NCT) and Connection Details
Turns ratio (T)
1 to 600
Voltage knee point (V
K
) 350 V
Magnetising current (Imag) @ V
K
50 mA
CT secondary resistance (R
CT
) 6 Ω
CT lead loop resistance (R
L
) 0.15 Ω max.
Protection and Automation Functions
5.21 87GH Restricted Earth-Fault Protection – High-Impedance
Reyrolle 7SR5, Transformer Protection Device, Device Manual 301
C53000-G7040-C015-1, Edition 11.2019

Table of Contents

Other manuals for Siemens Reyrolle 7SR5

Related product manuals