EasyManua.ls Logo

Siemens Reyrolle 7SR5 - Page 325

Siemens Reyrolle 7SR5
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The transformer has a phase shift of zero. To prevent undesired tripping for external faults a zero sequence
shunt is required, this is implemented by selecting star/delta interposing CT settings. The Interposing CT
Connection setting on all sets of current inputs must be set to the same Yd setting e.g. all Yd1, -30° or all
Yd11, 30°.
Transformer with Primary Connections Crossed on Both Windings
Yd11 Transformer Connected as Yd9 (90°)
The phase-shift between the W1 and W2 primary systems may necessitate that primary connections to each
winding of the transformer have to be crossed. Figure 5-62 shows a typical arrangement where a Yd11 trans-
former is arranged to give a primary system phase-shift of 90° by crossing of its main connections. There are 2
optional methods that can be used to for setting the 87T function element.
Solution 1
Figure 5-62 shows W1 and W2 CT secondary wiring crossed over to replicating the crossovers on the
transformer primary connections:
[dw_7SR5_function87Tsettingsexample10, 1, en_US]
Figure 5-62
AC Connections: Yd9, 90° Transformer – Non-standard Secondary Connections
An advantage of the above is that the relay can be set to correspond to the vector group shown on the
main transformer rating plate i.e. Yd11, +30° simplifying installation. This approach is also applicable
where the transformer is used to reverse the system phase sequence.
i
i
NOTE
‘Non-standard’ secondary wiring connections are used. Relay instruments will indicate ’transformer’ quanti-
ties rather than system quantities.
Protection and Automation Functions
5.22 87T Transformer Differential Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual 325
C53000-G7040-C015-1, Edition 11.2019

Table of Contents

Other manuals for Siemens Reyrolle 7SR5

Related product manuals