A81Hb5PHAR1.Mod
Information
Overfluxing Detector Enabled (Function Config) 0 1 1 x
Inhibit 81HBL5 x 0 1 x
81HBL5 Enabled 1 1 1 0
A81Hb5PHAR1.Mod.stVal 2 1 2 5
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value OK: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A81Hb5PHAR1.Health
Information
Protection Healthy 0 1
A81Hb5PHAR1.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A81Hb5PHAR1.Str
Information
81HBL5 PhA Pickup 0 1 x x
81HBL5 PhB Pickup 0 x 1 x
81HBL5 PhC Pickup 0 x x 1
A81Hb5PHAR1.Str.general 0 1 1 1
Information
81HBL5 PhA Pickup 0 1
A81Hb5PHAR1.Str.phsA 0 1
Information
81HBL5 PhB Pickup 0 1
A81Hb5PHAR1.Str.phsB 0 1
Information
81HBL5 PhC Pickup 0 1
A81Hb5PHAR1.Str.phsC 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Protection and Automation Functions
5.22 87T Transformer Differential Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual 333
C53000-G7040-C015-1, Edition 11.2019