A87BdPDIF1.Mod
Information
Differential Enabled (Function Config) 0 1 1 x
Inhibit 87BD x 0 1 x
87BD Enabled 1 1 1 0
A87BdPDIF1.Mod.stVal 2 1 2 5
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value OK: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A87BdPDIF1.Health
Information
Protection Healthy 0 1
A87BdPDIF1.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A87BdPDIF1.DifAClc
Information
Value
87BD Ia Operate A87BdPDIF1.DifAClc.phsA.instCVal.mag.f Measured Value Value
A87BdPDIF1.DifAClc.phsA.cVal.mag.f Measured Value Value
A87BdPDIF1.DifAClc.phsA.units.SIUnit 5 A
A87BdPDIF1.DifAClc.phsA.units.multiplier 0 1
Information Value
87BD Ib Operate A87BdPDIF1.DifAClc.phsB.instCVal.mag.f Measured Value Value
A87BdPDIF1.DifAClc.phsB.cVal.mag.f Measured Value Value
A87BdPDIF1.DifAClc.phsB.units.SIUnit 5 A
A87BdPDIF1.DifAClc.phsB.units.multiplier 0 1
Information Value
87BD Ic Operate A87BdPDIF1.DifAClc.phsC.instCVal.mag.f Measured Value Value
A87BdPDIF1.DifAClc.phsC.cVal.mag.f Measured Value Value
A87BdPDIF1.DifAClc.phsC.units.SIUnit 5 A
A87BdPDIF1.DifAClc.phsC.units.multiplier 0 1
A87BdPDIF1.Op
Information
87BD PhA Pickup 0 1 x x
87BD PhB Pickup 0 x 1 x
87BD PhC Pickup 0 x x 1
Protection and Automation Functions
5.22 87T Transformer Differential Protection
334 Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019