A24DTPVPH*.Health
Information
Device Healthy 0 1
A24DTPVPH*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A24DTPVPH*.Op
Information
24DT-n Operated 0 1
A24DTPVPH*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A24DTPVPH*.Str
Information
24DT-n Pickup 0 1
A24DTPVPH*.Str.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A24ITPVPH*.Mod
Information
24 Overexcitation Enabled (Function Config) x 0 1 1
Inhibit 24IT-1 1 x 0 0
24IT-1 Enabled x x 1 0
A24ITPVPH*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value OK: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
Protection and Automation Functions
5.2 24 Overexcitation Protection
156 Reyrolle 7SR5, Transformer Protection Device, Device Manual