Siemens Reyrolle 7SR54 - IEC 61850 Functional Information Mapping

Siemens Reyrolle 7SR54
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IEC 61850 Functional Information Mapping
A81Hb2PHAR1.Mod
Information
Inrush Detector Enabled (Function Config) 0 1 1 x
Inhibit 81HBL2 x 0 1 x
81HBL2 Enabled 1 1 1 0
A81Hb2PHAR1.Mod.stVal 2 1 2 5
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value OK: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A81Hb2PHAR1.Health
Information
Protection Healthy 0 1
A81Hb2PHAR1.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A81Hb2PHAR1.Str
Information
81HBL2 PhA Pickup 0 1 x x
81HBL2 PhB Pickup 0 x 1 x
81HBL2 PhC Pickup 0 x x 1
A81Hb2PHAR1.Str.general 0 1 1 1
Information
81HBL2 PhA Pickup 0 1
A81Hb2PHAR1.Str.phsA 0 1
Information
81HBL2 PhB Pickup 0 1
A81Hb2PHAR1.Str.phsB 0 1
Information
81HBL2 PhC Pickup 0 1
A81Hb2PHAR1.Str.phsC 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
5.22.6
Protection and Automation Functions
5.22 87T Transformer Differential Protection
332 Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019

Table of Contents