EasyManua.ls Logo

Siemens Reyrolle 7SR54 - IEC 61850 Functional Information Mapping

Siemens Reyrolle 7SR54
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions > Protection > 46 > 46IT-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Char DTL
IEC-NI, IEC-VI
IEC-EI, IEC-LTI
ANSI-EI, ANSI-MI
ANSI-VI
IEC-NI
TMS (IEC/ANSI) 0.025 to 1.6, Δ 0.01
1.6 to 5, Δ 0.1
5 to 100, Δ 1
1
Delay (DTL) 0 to 20 s Δ 0.01 s 5 s
Reset IEC/ANSI Decaying
0 to 60 s Δ 1 s
0 s
IEC 61850 Functional Information Mapping
A46DTPTOC*.Mod
Information
46 NPS Overcurrent Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A46DTPTOC*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A46DTPTOC*.Health
Information
Device Healthy 0 1
A46DTPTOC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
5.7.6
Protection and Automation Functions
5.7 46 Negative-Sequence Overcurrent Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual 185
C53000-G7040-C015-1, Edition 11.2019

Table of Contents

Related product manuals