Siemens Reyrolle 7SR54 - 21 LB Load Blinder; Phase Load Blinder (21 LB-3 P); Single Phase Load Blinder (21 LB-1 P)

Siemens Reyrolle 7SR54
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21LB Load Blinder
3 Phase Load Blinder (21LB‑3P)
Reference
Parameter Value
I
2 set
I
2
level setting 0.05 ⋅ I
rated
to 5 ⋅ I
rated
V
2 set
V
2
level setting 1 V to 110 V
φ+ set Angle +ve setting 5° to 85°
φ- set Angle –ve setting 5° to 85°
Z
set
Impedance setting 1 Ω to 100 Ω
Operate and Reset Level
Attribute Value
V
op
V
1
operate level V
set
: ± 2 % or ± 0.5 V
V
1
reset level 110 % V
1 op
: ± 5 % V
rated
I
op
I
2
operate level I
set
: ± 5 % or ± 1 % I
rated
Impedance Z
set
: ± 5 % or ± 0.1 Ω
Repeatability ± 1 %
Operate Angle
Attribute
Value
φ
op
Operating angle Forward φ+ set ± 5° to
φ- set ± 5°
Reverse (180° - φ+ set) ± 5° to
(180° + φ- set) ± 5°
Single Phase Load Blinder (21LB‑1P)
Reference
Parameter
Value
I
0 set
I
0
level setting 0.05 ⋅ I
rated
to 5 ⋅ I
rated
V
1 set
V
1
level setting 1 V to 110 V
φ+ set Angle +ve setting 5° to 85°
φ- set Angle –ve setting 5° to 85°
Z
set
Impedance setting 1 Ω to 100 Ω
Operate and Reset Level
Attribute
Value
V
op
V
1
operate level V
set
: ± 2 % or ± 0.5 V
V
1
reset level 110 % V
1 op
: ± 5 % V
rated
I
op
I
0
operate level I
set
: ± 5 % or ± 1 % I
rated
Impedance Z
set
: ± 5 % or ± 0.1 Ω
Repeatability ± 1 %
10.2
10.2.1
10.2.2
Technical Data
10.2 21LB Load Blinder
Reyrolle 7SR5, Transformer Protection Device, Device Manual 457