[dw_7SR5_function87GHApplicationAndSettingNotes4, 1, en_US]
Figure 5-47 REF Relay Circuit
Settings Menu
Functions > Function Config
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
87GH Restricted EF Enabled
Disabled
Disabled
Functions > Protection > 87 > Gn 87GH-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Element Enabled
Disabled
Disabled
Setting 0.02 to 0.95, Δ 0.005 I
rated
0.2 I
rated
Delay (DTL) 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0 s
IEC 61850 Functional Information Mapping
A87GHPTOC*.Mod
Information
87GH Restricted EF Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A87GHPTOC*.Mod.stVal 5 5 2 1
5.21.5
5.21.6
Protection and Automation Functions
5.21 87GH Restricted Earth-Fault Protection – High-Impedance
304 Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019