EasyManua.ls Logo

Siemens Reyrolle 7SR54 - Page 302

Siemens Reyrolle 7SR54
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Calculation of Required Stability Voltage Limits
The assigned through fault current is 31.5 kA.
[fo_function87GHApplication&SettingsFunction13, 1, en_US]
[fo_function87GHApplication&SettingsFunction14, 1, en_US]
[fo_function87GHApplication&SettingsFunction15, 1, en_US]
Calculation of Stabilizing Resistor Value
The required relay setting I
set
can be calculated from:
[fo_function87GHApplication&SettingsFunction21, 1, en_US]
[fo_function87GHApplication&SettingsFunction22, 1, en_US]
[fo_function87GHApplication&SettingsFunction23, 1, en_US]
The magnetizing current is dependent on the relay operate voltage (V
set
). This is not finalized yet so a provi-
sional value is chosen from the above i.e. 107.1 < V
set
< 150
Say V
setprov
= 120 V. From CT magnetizing curve: At 120 V I
MAGLCT
= 9 mA and I
MAGNCT
= 12 mA
[fo_function87GHApplication&SettingsFunction24, 1, en_US]
[fo_function87GHApplication&SettingsFunction25, 1, en_US]
Metrosil Specification
C Value
V
set
= 120 V (i.e. > 100 V) so a C value of 1000 is chosen
Short Time Power Rating
Using the empirical formula
[fo_function87GHApplication&SettingsFunction12, 1, en_US]
Protection and Automation Functions
5.21 87GH Restricted Earth-Fault Protection – High-Impedance
302 Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019

Table of Contents

Related product manuals