EasyManua.ls Logo

Siemens Reyrolle 7SR54 - Page 469

Siemens Reyrolle 7SR54
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Attribute Value
Repeatability ± 1 % or ± 20 ms
Overshoot time < 40 ms
Disengaging time < 90 ms
Technical Data
10.10 47 Sequence Overvoltage Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual 469
C53000-G7040-C015-1, Edition 11.2019

Table of Contents

Related product manuals