Siemens Building Technologies Electronic Air / Fuel Ratio Control System CC1P7873.1en
HVAC Products 18 Notes on the commissioning of a burner 15.10.2002
18.3 Setting report
Plant: .................................................................................................................................................
Date: ..................................................................................................................................................
Fuel 1: .............................................................. Fuel 2: .....................................................................
Fuel 1 Fuel 2
Number of auxiliary actuators * Aux1Act..................... (½)
Second auxiliary actuator (Y5 / Y6) * Aux2Act..................... (on /
off)
Interval t4 * Interva ....................... (s)
Running time of auxiliary actuator 1 (AUX1) Aux1Tim .................... (s) ...................................(s)
Running time of auxiliary actuator 2 (AUX2) * Aux2Tim .................... (s)
Position of end switches «Fully closed»
(Close)
Aux1Pos.................... (V) ...................................(V)
* Aux2Pos.................... (V)
Position of end switches «Fully open»
(Open)
Aux1Pos.................... (V) ...................................(V)
* Aux2Pos.................... (V)
Compensation of hysteresis Hyster........................ (V) ...................................(V)
Impact of correcting variable Disturb....................... (%) ...................................(s)
Impact of correcting variable on actuator
(AUX2)
Aux2Dis..................... (on /
off)
...................................(on /
off)
* Settings also apply to fuel 2