EasyManua.ls Logo

Siemens RVW26.000B27 - Technical Data; General Data

Siemens RVW26.000B27
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68/69
Siemens Building Technologies Electronic Air / Fuel Ratio Control System CC1P7873.1en
HVAC Products 19 Technical data 15.10.2002
19 Technical data
Operating voltage AC 230 V ±15 %
Frequency 50 / 60 Hz ±6 %
Power consumption < 15 VA
Protection standard of housing
- Front
- Base
IP 42 DIN 40050
IP 10 DIN 40050
Insulation class II VDE 0631
Mounting position optional
Switching capacity of relay «L-Q1»
· Voltage
· Current
operating voltage
2 A
Switching capacity of relay «Q4...Q5 / H»
· Voltage
· Current
AC 24...265 V
at AC 230 V: 0.005...2 A
at AC 24 V: 0.02...2 A
Switching capacity of control outputs
«Y3...Y6, Y8»
· Voltage
· Current
operating voltage
5...150 mAeff
Control inputs «Q2, Q3, Y10, Y20, F1, F2»
· Voltage ON
· Voltage OFF
· Current ON
AC 187...265 V
< AC 50 V
approx. 0.4 mA
Signal inputs «B1...B4, U1»
· Voltage
· Impedance
· Perm. humming voltage
DC 0...10 V
130 K
W
max. AC 50 mV
Signal output «X2 / U3»
· Voltage
· Impedance
DC 0...10 V
25 KW
Signal output «U10»
· Voltage
· Current
DC 10 V
max. 50 mA
Signal output «X1»
· Voltage
· Impedance
DC 0...10 V
100 W
Signal output «X3»
· Voltage
· Impedance
DC 0...10 V
470 W
Signal output +5 V auxiliary voltage; max. load 1 mA
Suitable feedback potentiometers 1000 W total resistance
(perm. 800...1500
W)
(refer to «Product range overview»)
Actuator running times 30...60 s
(the various actuators may have different
running times, refer to «Product range
overview»)
General data

Table of Contents

Related product manuals