5.2.3 2-stage burner, 3-position output
In area (1), the thermostat function is active. In area (2), the RWF50.2 as a 2-position
controller acts on the second stage via relay K2 (OPEN) and relay K3 (CLOSE) by
switching on at switch-on threshold HYS1 and switching off at switch-off threshold HYS2.
7866d07/0911
Figure 10: Control sequence of 2-stage burner, 3-position output
In area (3), the actual value exceeds the upper switch-off threshold HYS3 and the
controller shuts down the burner (B). The controller only starts low-fire operation when
the actual value falls again below switch-on threshold HYS1. If the response threshold
(q) is exceeded, the controller switches to high-fire operation (A).
Reference!
See chapter 5.5 Response threshold (q).
Only RWF50.2