8.6 Display diSP
By configuring the position of the decimal point and automatic changeover (timer), both
LED indications can be adapted to the respective requirements. Timeout
tout for
operation and the locking of levels can be configured as well.
ConF dISP
Parameter Value/
selection
Description
Display value for upper display
0 Switched off
1 Analog input InP1
4 Controller’s angular positioning
6 Setpoint
Upper display
diSU
Upper display
7 End value with thermal shock protection
Display value for lower display
0 Switched off
1 Analog input InP1
4 Controller’s angular positioning
6 Setpoint
Lower display
diSL
Lower display
7 End value with thermal shock protection
Timeout
tout
0...
180...
255
Time (s) on completion of which the controller returns automatically to the
basic display, if no button is pressed
0 No decimal place
1 One decimal place
2 Two decimal places
Decimal point
dECP
Decimal point
If the value to be displayed cannot be shown with the programmed decimal
point, the number of decimal places is automatically reduced. If the
measured value drops again, the number of decimal places is increased
until the programmed value is reached
0 No locking
1 Locking of configuration level
2 Locking of parameter level
Locking of levels
CodE
3 Locking of keyboard