5.4 Predefined setpoint
The setpoint is predefined within the selected setpoint limits via the buttons or the
ACS411 software. Using an external contact, the setpoint can also be shifted or
changed over.
Reference!
See chapter 8.5 Binary functions binF.
Depending on the function selected for the binary input, the effective controller setpoint
can change between setpoint SP1 and setpoint SP2 or can be shifted by the amount of
dSP. A contact at binary input D1 controls the changeover or shift.
The values for setpoints SP1, SP2 and dSP are to be entered at the operating level.
Reference!
See chapter 6 Operation.
Contact at binary input D1
Open: 0 Closed: 1
D1
DG
D1
DG
Chapter 4.3 Assignment of pins
SP1
SP2
dSP
0
1
0
1
+
0
1
2
SPH oLHi
/
SPL oLLo
/
Active setpoint
Chapter 8.2 Controller
Cntr
Function of
binary input D1
bin1
None (factory-set)
Setpoint changeover
Setpoint shift
0
1
2
Chapter 8.5 Binary functions
binF
7866a11e/0412
Figure 12: Setpoint changeover or setpoint shift
Setpoint changeover
or setpoint shift