EasyManuals Logo

Siemens RWF55.51A9 User Manual

Siemens RWF55.51A9
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
51/93
Building Technologies Division User Manual RWF55... CC1U7867en
Infrastructure & Cities Sector 8 Configuration ConF 05.11.2013
Parameter Value/
selection
Description
Filter time constant
dF1
Digital filter
0.0...
0.6...
100.0...
Is used to adapt the digital 2nd order input filter (time in s; 0 s = filter off)
If the input signal changes abruptly, about 26% of the change are captured
after a time corresponding to the filter time constant dF (2 x dF: approx. 59%;
5 x dF: approx. 96%)
When the filter time constant is great:
- Great attenuation of interference signals
- Slow response of actual value display to changes of the actual value
- Low limit frequency (low-pass filter)
Temperature unit
Unit
Temperature unit
1 Degrees Celsius
2
Degrees Fahrenheit
Unit of temperatures

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RWF55.51A9 and is the answer not in the manual?

Siemens RWF55.51A9 Specifications

General IconGeneral
BrandSiemens
ModelRWF55.51A9
CategoryController
LanguageEnglish

Related product manuals