86/93
Building Technologies Division User Manual RWF55... CC1U7867en
Infrastructure & Cities Sector 14 Technical data 05.11.2013
14.7 Environmental conditions
Storage
DIN IEC 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -40...70 °C
Humidit
y
<95% r.h.
Transport
DIN IEC 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -40...70 °C
Humidity <95% r.h.
Operation
DIN IEC 60721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
Temperature range
-20...50°C
Humidity <95% r.h.
Installation altitude Max. 2000 m above sea level
Attention!
Condensation, formation of ice and ingress of water are not permitted!
14.8 Segment display
Height of numerals
- Upper display 10 mm
- Lower display 7 mm
Color
- Upper display Red
- Lower display Green
Digits 4 (including 0, 1 or 2 decimal places,
configurable)
Range of display -1999...9999
14.9 Standards and certificates
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Low-voltage directive, to DIN EN 60730-1
2004/108/EC
2006/95/EC
ISO 9001: 2008
Cert. 00739
ISO 14001: 2004
Cert. 38233