4 Configuration/Engineering
EtherNet/IP Scanner
Entry-ID: 109782314, V1.1.0, 04/2021
26
© Siemens AG
2021 All rights reserved
Step
Instruction
Result
4.
Open the EDS file of the second
adapter with you text editor program
(e.g. Notepad).
Note the relevant data from the
differerent sections
The following data are used in this
application example
From sections
[Device]
VendorCode = 1251
ProductType = 12
ProductCode = 1200
Revision = 1.004
[Params]
Output Size = 64 Bytes
Input Size = 64 Bytes
RPI = 25 ms (25.000µs)
[Connection Manager]
Instance ID = 104 (68hex)
OT Assembly ID = 102 (66hex)
TO Assembly ID = 101 (65hex)
5.
Transfer the noted data to the
EnetIOSystem data block
as a result, the EnetIoSystem should
look like the below: