4 Configuration/Engineering
EtherNet/IP Scanner
Entry-ID: 109782314, V1.1.0, 04/2021
© Siemens AG
2021 All rights reserved
Open the EDS file of the second
adapter with you text editor program
(e.g. Notepad).
Note the relevant data from the
differerent sections
The following data are used in this
application example
From sections
[Device]
• VendorCode = 1251
• ProductType = 12
• ProductCode = 1200
• Revision = 1.004
[Params]
• Output Size = 64 Bytes
• Input Size = 64 Bytes
• RPI = 25 ms (25.000µs)
[Connection Manager]
• Instance ID = 104 (68hex)
• OT Assembly ID = 102 (66hex)
• TO Assembly ID = 101 (65hex)
Transfer the noted data to the
EnetIOSystem data block
as a result, the EnetIoSystem should
look like the below: