6 LCCF_EnetScanner block
EtherNet/IP Scanner
Entry-ID: 109782314, V1.1.0, 04/2021
38
© Siemens AG
2021 All rights reserved
6.1.1 Block status messages
The LCCF_EnetScanner block reports a status information to the user, which
follows a standardized pattern.
The status code is split into the error flag and a status information value.
Table 6-3: Error and status message format
15
14
12
11
8
7
0
Error
Info/ Warning
Class Code
Specific Status Codes
16#7 = Information
16#8 = Error
0 = Information
2 = Parameter
related
4 = Internal Cause
6 = External Cause
The LCCF_EnetScanner reports specific status codes. They are listed and
explained in the following table.
Table 6-4: status messages
Valid
Busy
Error
Status
Code
(in hex)
Cause
Remedy
TRUE
TRUE
FALSE
16#0000
Success/ OK
--
FALSE
FALSE
FALSE
16#7000
No Call/ Idle
Block is called with
enable = FALSE.
Create rising edge on
enable to start
execution
FALSE
TRUE
FALSE
16#7001
Initial call
Block starts
initialization and
performs parameter
check
TRUE
TRUE
FALSE
16#7002
Follow Up call
Block continues
operation
TRUE
TRUE
FALSE
16#7202
More data areas
have been
parameterized,
than adapter have
been configured
Adjust the array
boundaries for the data
area to be the same as
the adapter definitions.
When keep operating,
the excessive data
areas are not touched
and remain
unchanged.
TRUE
TRUE
FALSE
16#72x7
Parameterized
RPI was at least
once exceeded by
the adapter[x].
This warning indicates
an overload and should
be avoided by
increasing the RPI.
TRUE
TRUE
FALSE
16#72x8
Scanner cannot
realize the desired
update rate for
adapter[x]
This warning indicates
an overload situation
on the scanner side
and should be avoided.
This can be achieved
by increasing the RPI.