6 LCCF_EnetScanner block
EtherNet/IP Scanner
Entry-ID: 109782314, V1.1.0, 04/2021
39
© Siemens AG
2021 All rights reserved
Valid
Busy
Error
Status
Code
(in hex)
Cause
Remedy
TRUE
TRUE
FALSE
16#76x2
Overload
situation, updates
for adapters may
have been lost
This warning indicates
an overload situation
on the scanner side.
This can be avoided by
increasing the
“Communication load”
setting in the CPU
properties or
increasing the call up
interval of the used
cyclic interrupt.
FALSE
FALSE
TRUE
16#8006
Cannot setup I/O
socket.
It appears that the
required UDP
connection resource
cannot be acquired
from the system.
Check and make sure,
there are at least one
unused UDP resource
available. Consult the
technical data for the
used CPU model to
learn how many such
resources the CPU
has.
FALSE
FALSE
TRUE
16#8201
Invalid interface
specified
The specified interface
doesn’t support the
acquisition of operation
relevant information.
This interface cannot
be used to be operated
as scanner.
Specify a different
interface.
FALSE
FALSE
TRUE
16#8202
Number of
configured
adapters exceed
maximum
possible adapters
Reduce the number of
adapters in this system
to the maximum
allowed number.
FALSE
FALSE
TRUE
16#8203
Number of
configured data
areas is lower
than number of
configured
adapters.
Adjust the array
boundaries to be
identical for both
number of configured
adapters and available
data areas.
FALSE
FALSE
TRUE
16#82x4
Invalid OT size
configuration for
adapter [x]
Verify that only one of
the data size flags are
set.
FALSE
FALSE
TRUE
16#82x5
Invalid TO size
configuration for
adapter [x]
Verify that only one of
the data size flags are
set.
FALSE
FALSE
TRUE
16#82x6
Invalid
configuration data
size configuration
for adapter [x]
Verify that only one of
the data size flags are
set.
FALSE
FALSE
TRUE
16#82x7
Parameterized
input buffer is
Adjust the configured
TO direction data