Connecting
5.1 Safety when connecting up
SCALANCE X-300
44 Compact Operating Instructions, 05/2016, A5E00982643-14
Safety notices when using the device according to Hazardous Locations (HazLoc)
If you use the device under HazLoc conditions you must also keep to the following safety
notices in addition to the general safety notices for protection against explosion:
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS.
Safety notices for use according to ATEX and IECEx
If you use the device under ATEX or IECEx conditions you must also keep to the following
safety notices in addition to the general safety notices for protection against explosion:
Take measures to prevent transient voltage surges of more than 40% of the rated voltage.
This is the case if you only operate devices with SELV (safety extra-low voltage).
Before connecting up and commissioning the device, read the information in the section
Safety instructions (Page 11)
Note
Commissioning devices with redundancy mechanisms
If you use redundancy mechanisms ("HRP" media redundancy or "MRP" and/or redundant
coupling of rings over standby coupling), open the redundant path before you insert a new or
replacement device in an operational network. A bad configuration or attachment
Ethernet cables to incorrectly configured ports causes overload in the network and a
breakdown in communication.
A device may only be inserted in a network and connected in the following situations:
HRP/MRP:
The ring ports of the device being inserted in the ring were configured as ring ports. The
required redundancy mode must also be enabled (see "Configuration Manual
SCALANCE X-300 / X-400", section "X-300 Ring Configuration"). If the device is intended
to operate as the redundancy manager, "Redundancy manager enabled" must also be
set.
Standby coupling:
"Standby connection" must be "enabled" and the "Standby connection name" must match
the name of the partner device. You will also need to configure the port with "Enable
Standby Port Monitoring" (see "Configuration Manual SCALANCE X-300 / X-
"X-300/X-400 Standby Mask").