Applications 
  3.3 Motor protection applications of 3VA molded case circuit breakers 
3VA molded case circuit breakers with IEC certificate 
Manual, 03/2019, A5E03603177010-03 
145 
 
3VA molded case circuit breakers for starter protection 
 
When the 3VA molded case circuit breaker is used as a starter protection circuit breaker, the 
3VA only takes on the short-circuit protection function of the motor feeder. The overload 
protection of the motor feeder is provided by an overload relay, such as 3RB, or by a motor 
management device, such as SIMOCODE. 
Functional switching is performed by the contactor. 
Two different device ranges are available for starter protection applications: 
●  3VA1 starter protection circuit breaker with a magnetic trip unit for standard motor feeders 
with a rated conditional short-circuit current I
q
 up to 100 kA 
●  3VA2 starter protection circuit breaker with electronic trip unit for high-end motor feeders 
with a rated conditional short-circuit current I
q
 up to 150 kA 
You will find the tested device combinations in the Siemens Industry Online Support 
(https://support.industry.siemens.com/cs/ww/en/view/109483387
). 
The short-circuit release of the TM110M magnetic trip unit is not adjustable. In this case the 
short-circuit release is permanently set to 16 times the rated current I
n
.