Description   
2.6 Protection system 
  3VA molded case circuit breakers with IEC certificate 
72  Manual, 03/2019, A5E03603177010-03 
 
To design a low-voltage switchboard in accordance with the valid rules, the system planner 
needs to dimension the protection settings of the molded case circuit breakers. 
The settings selected for the trip unit of a molded case circuit breaker depend on the type of 
equipment to be protected, e.g. switchboard and applications. 
Tripping characteristics up to a tripping time of ≥ 1 ms are represented graphically. In order 
to ease the coordination of different protection devices, the current is specified as a multiple 
of the current setting value and the time is specified in seconds. 
Tripping characteristics for thermal-magnetic trip units 
Characteristics are displayed graphically in the double-log coordinate system (cf. 
IEC 60947-2, paragraph 4.7.4 and IEC 60269-1). The ratio of current to time is 2: 1. 
Tripping characteristics for electronic trip units 
Characteristics are displayed graphically in the double-log coordinate system (cf. 
IEC 60269-1). The ratio of current to time is 1: 1. 
 
  Response threshold of the long-time delayed 
protection, thermal 
  Delay of the short-time delayed protection 
  Response threshold of the long-time delayed 
protection 
  Response threshold of the instantaneous 
protection 
  Delay of the long-time delayed protection  L  Overload range 
  Response threshold of the short-time delayed 
protection 
S  Short-time delayed short-circuit current 
range 
  I
2
t characteristic ON/OFF of the short-time 
delayed protection 
I  Instantaneous short-circuit current range