Description   
2.5 Standards and guidelines 
  3VA molded case circuit breakers with IEC certificate 
58  Manual, 03/2019, A5E03603177010-03 
 
You can find information on the available certification (CE, UL, CSA, FM, marine approvals) 
on the Internet (http://support.automation.siemens.com/WW/view/en/54137334/134200
). 
In the Entry List you can use the certificate type (e.g. general product approval, explosion 
protection, test certificates, shipbuilding) as a filter criterion. 
 
Ambient conditions 
Pollution degree 
Operation of the 3VA1 and 3VA2 molded case circuit breakers is approved in accordance 
with IEC / EN 60947-1 and IEC / EN 60664-1 for pollution degree 3. 
3VA molded case circuit breakers are used at ambient temperatures from -25 °C to +70 °C. 
Derating (reduction in rated operational current) is required at temperatures above +50 °C. 
You will find more information on the applicable derating factors in chapter Derating and 
temperature compensation (Page 628). 
The permissible storage temperature in original Siemens packaging is between -40 °C 
and +80 °C. 
Special climatic requirements 
3VA molded case circuit breakers can also be used under harsh conditions. 
Harsh conditions of storage, transportation and stationary use 
The molded case circuit breakers have been tested according to the relevant special test 
procedures defined in IEC / EN 60947-1, Annex Q for 
 applications. 
This class covers the areas MC3 + CC2 + SC1: 
●  Ambient temperature 
●  Humidity 
●  Vibration environment 
●  Shock environment 
These ambient conditions can be referred to as "Open deck, damp and cold atmosphere 
without salt spray" or "Difficult, non-marine conditions".