Service and maintenance 
  5.3 Maintenance following tripping of a molded case circuit breaker 
3VA molded case circuit breakers with IEC certificate 
Manual, 03/2019, A5E03603177010-03 
537 
 
Maintenance following tripping of a molded case circuit breaker 
If a 3VA molded case circuit breaker trips on overcurrent (overload, short circuit) or residual 
current (ground fault or via residual current device), the cause of the trip must be identified 
and rectified before the molded case circuit breaker is switched on again.  
In the case of 3VA1 molded case circuit breakers with thermal-magnetic trip units, the cause 
of tripping can be determined by means of the SAS short circuit alarm switch. With 3VA2 
molded case circuit breakers, the cause of tripping can be output via the EFB300 external 
function box. With electronic trip units 5-series and 8-series ETUs, the cause of tripping can 
be indicated on the LCD and optionally transferred via communication modules. 
An inspection as described in chapter Regular maintenance (Page 535) should be carried 
out every time the molded case circuit breaker is tripped by the trip unit. In addition, all black 
residues on the molded case circuit breaker must be removed as they might contain 
conductive particles. The molded case circuit breaker should then be switched on and off 
without load at least five times.