EasyManua.ls Logo

Siemens SENTRON 3VA1 - ETU860 M Electronic Trip Unit

Siemens SENTRON 3VA1
676 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Applications
3.3 Motor protection applications of 3VA molded case circuit breakers
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03
161
3.3.4.2
ETU860M electronic trip unit
Motor protection - function LSIG
The ETU860M electronic trip unit features:
Adjustable parameter setting I
r
for overload protection (L)
Adjustable parameter setting I
sd
for short-time delayed short circuit protection (S)
Fixed parameter setting t
sd
for short-time delayed short circuit protection (S), t
sd
= 0.03 s
Adjustable parameter setting I
i
for short-circuit protection (I)
Adjustable parameter settings I
g
and t
g
for ground-fault protection (G)
Adjustable parameter setting T
c
for the trip class or tripping time T
p
Adjustable parameter setting for phase unbalance from 5 to 50% / OFF, t
unbal
Adjustable parameter settings I
b
and t
b
for blocking protection
Adjustable parameter settings I
<<
and t
<<
for idle running protection

Table of Contents