Accessories   
4.2 Internal accessories 
  3VA molded case circuit breakers with IEC certificate 
204  Manual, 03/2019, A5E03603177010-03 
 
Auxiliary releases allow remote electrical tripping of the circuit breaker. They can be used to 
monitor control or main circuits in order to implement a protective system against accidental 
restart following a power failure, for example. 
Auxiliary releases therefore perform a main circuit monitoring function in addition to the main 
circuit monitoring performed by the trip unit. 
Auxiliary releases are extremely easy to install. No tools are required because these 21 mm 
wide components are simply snapped into place in the accessory compartments to the left 
and right of the handle. The accessories are connected by screw terminals for auxiliary 
conductors with a cross-section of up to 1.5 mm
2
. The terminals are mounted on the front of 
the unit for easy access.  
The shunt trips are suitable for use in electrical interlocks. An attempt to switch on a circuit 
breaker while the interlock voltage is applied to the shunt trip leads to a so-called "no-load 
switching operation", i.e. the basic breaker always returns to the TRIP position and the main 
contacts never close. 
 
 
All auxiliary releases are reverse-polarity-protected. 
 
Shunt trips of type STL can be fitted in the left-hand accessory compartment as an 
alternative to an undervoltage release. The units are available with five rated voltages in the 
following range: 
●  24 to 600 V AC 50/60 Hz 
●  12 to 250 V DC 
They have a maximum power consumption of 58 VA which is significantly lower than the 
power consumption of the flexible shunt trip versions. 
Switches (permanent signal) or momentary push-buttons (minimum signal duration 40 ms) 
may be used to control shunt trips. 
Shunt trip left STL (EI) for electrical interlocks 
Shunt trips of the type STL (EI) can be used to implement electrical interlocks between two 
molded case circuit breakers. The interlocking auxiliary release prevents short-time contact 
between the main contacts during a switch-on attempt. 
Shunt trip STL (EI) is available with a rated voltage of 24 V DC.