EasyManua.ls Logo

Siemens SENTRON 3VA1 - ETU350 M Electronic Trip Unit

Siemens SENTRON 3VA1
676 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Applications
3.3 Motor protection applications of 3VA molded case circuit breakers
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03
155
3.3.3
ETU350M electronic trip unit
Motor protection - function LSI
The ETU350M electronic trip unit features:
Adjustable parameter setting I
r
for overload protection (L)
Adjustable parameter setting I
sd
for short-time delayed short circuit protection (S)
Fixed parameter setting t
sd
for short-time delayed short circuit protection (S), t
sd
= 0.03 s
Fixed parameter setting I
i
for short-circuit protection (I), I
i
= 15 x I
r
Adjustable parameter setting T
c
for the trip class
Fixed parameter setting for phase unbalance of 40%
Permanently active thermal memory, cannot be deactivated
ETU350M parameters